Technical data for design verification |
|
|
|
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890 |
|
|
|
Individual enclosure for wall mounting |
PV |
CO |
23
|
Starting enclosure for wall mounting |
PV |
CO |
22
|
Middle enclosure for wall mounting |
PV |
CO |
21
|
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890 |
|
|
|
Individual enclosure for wall mounting |
PV |
CO |
47
|
Starting enclosure for wall mounting |
PV |
CO |
45
|
Middle enclosure for wall mounting |
PV |
CO |
42
|
IEC/EN 61439 design verification |
|
|
|
10.2 Strength of materials and parts |
|
|
|
10.2.2 Corrosion resistance |
|
|
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
|
|
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
|
|
Meets the product standard's requirements.
|
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
|
|
960 °C; meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
|
|
Not relevant to indoor installations.
|
10.2.5 Lifting |
|
|
20 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
|
10.2.6 Mechanical impact |
|
|
IK10
|
10.2.7 Inscriptions |
|
|
Meets the product standard's requirements.
|
10.3 Degree of protection of ASSEMBLIES |
|
|
IP65, with cover
|
10.4 Clearances and creepage distances |
|
|
Is the panel builder's responsibility.
|
10.5 Protection against electric shock |
|
|
Protection class 2, therefore not applicable.
|
10.6 Incorporation of switching devices and components |
|
|
Is the panel builder's responsibility.
|
10.7 Internal electrical circuits and connections |
|
|
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
|
|
Is the panel builder's responsibility.
|
10.9 Insulation properties |
|
|
|
10.9.2 Power-frequency electric strength |
|
|
Ui = 1000 V AC
|
10.9.3 Impulse withstand voltage |
|
|
8 kV
|
10.9.4 Testing of enclosures made of insulating material |
|
|
Meets the product standard's requirements.
|
10.10 Temperature rise |
|
|
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
|
|
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
|
|
Is the panel builder's responsibility.
|
10.13 Mechanical function |
|
|
Meets the product standard's requirements.
|