Datasheet - CI23E-125

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Insulated enclosure, +knockouts, HxWxD=250x187.5x150mm
Part no.  CI23E-125
Catalog No.  019570
 
EL-Nummer (Norway)  4132075

Delivery program
Dimensions
  mm
Product range
    Ci insulated enclosures
Basic function
    Basic enclosures
Product function
    Individual enclosures
Single unit/Complete unit
    Single unit
Degree of Protection
    IP65
Description
    With metric knockouts in all sides of the enclosure
Include fixing straps for wall mounting
Sealable cover fasteners
Full-area knockouts in the sides
can be converted to a distribution board enclosure
Colour
    RAL 7032, pebble grey (base)
transparent, opaque (cover)
Width
  mm 187.5
Height
  mm 250
Depth
  mm 150
Mounting depth with mounting plate
  mm 125
Mounting depth for mounting rail 7.5 mm height
  mm 117.5
Mounting depth for mounting rail 15 mm height
  mm 110
Enclosure depth
     
Legend for the graphic
    Dimensions from top:
Mounting depth with mounting plate
Mounting depth for mounting rail 7.5 mm height
Mounting depth for mounting rail 15 mm height
Enclosure depth
Enclosure depth
  mm
Type cover
    Transparent
Model base
    knockout
For use with
    PKZM0-…/S(E)00
+NHI or NHI…S
+NHI-E
+U or A (undervoltage or shunt release)
+R(H)
+L-PKZ0 (2 off)
Notes 
A
 

1 x M32/20

6 x M20

2 x M16

B
 

2 x M32/20

4 x M25/16

4 x M20

4 x M16

Technical data
General
Standards
    IEC/EN 60529
EN 50262
DIN 43656
DIN 43660
EN 60439-4 for CI...X individual enclosures with combined distribution boards from Ci enclosures up to 680 A.
Can thus be used for socket combinations and as component for construction site distribution boards.
Climatic proofing
    Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
  °C -40 - +80
Degree of Protection
    IP65
Power loss
     
Max. radiated heat dissipation with separate mounting, ambient air temperature +20 °C
  W 33
Max. radiated heat dissipation in distribution board combination  to VDE 0660 Part 500
  W 25
Notes
    When calculating the heat dissipation, the quadratic relationship of current with the rated diversity factor a must be considered.
Pv = I2 x R
Pv’ = Pv x a2
If no data is available concerning the load relationships of the individual circuits, the rated diversity factor is selected conform to VDE 0660 Part 500.
additional technical data for UL-/CSA- approved devices
    see UL-report File No. E54120
Operating and ambient conditions to VDE 0660 Part 500
     
Colour
     
Base
    RAL 7032, pebble grey
Housing body
    Transparent, colourless or RAL 7032, pebble grey
Material characteristics
Material
    glass-fibre reinforced polycarbonate (base)
non-reinforced polycarbonate (cover)
Halogen free
Surface treatment
    Resistant to corrosion
Colour
    RAL 7032, pebble grey (base)
transparent, opaque (cover)
Colour
     
Base
    RAL 7032, pebble grey
Housing body
    Transparent, colourless or RAL 7032, pebble grey
Material properties
Electrical
     
Track resistance
    KB160, KC175 (base, to IEC 60112)
KB100, KC200 (cover, to IEC 60112)
Surface resistance to IEC 60093
  Ω x 1013 1
Dielectric strength to IEC 60243-1
  kV/mm 30
Thermal
     
Temperature resistant
    -40 °C - 120 °C (enclosure)
85 °C (enclosure bolt)
80 °C (gasket)
Mechanical
     
Impact resistance
    IK10 according to EN 50102
Loading capacity
  kg/m2 5
Chemical resistance
     
Chemical resistant
    Resistant against: Acids < 10 %, mineral oil, alcohol, gasoline, greases, salt solutions
Partly resistant to: Acids > 10 %
Not resistant to: alkalis, benzene
Atmospheric
     
Saline spray
    IEC 60068-2-11
UV resistance
    Beneath protective shield
Water consumption to DIN EN ISO 62
  % 0.29
Flammability characteristics
     
Flammability classification according to UL94
    V1 (base)
V2 (cover)
Design verification as per IEC/EN 61439(Show features)(Hide features)
Dimensions
CI23E