| range of product |
TeSys D
|
|
| range |
TeSys
|
|
| product name |
TeSys D
|
|
| product or component type |
Contactor
|
|
| device short name |
LC1D
|
|
| contactor application |
Resistive loadMotor control
|
|
| utilisation category |
AC-1AC-3AC-4
|
|
| poles description |
3P
|
|
| pole contact composition |
3 NO
|
|
| System Voltage |
<= 300 V DC power circuit<= 690 V AC 25...400 Hz power circuit
|
|
| [Ie] rated operational current |
40 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit60 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
|
|
| motor power kW |
18.5 kW at 380...400 V AC 50/60 Hz AC-322 kW at 500 V AC 50/60 Hz AC-330 kW at 660...690 V AC 50/60 Hz AC-311 kW at 220...230 V AC 50/60 Hz AC-39 kW at 400 V AC 50/60 Hz AC-422 kW at 415...440 V AC 50/60 Hz AC-3
|
|
| motor power hp |
5 hp at 230/240 V AC 50/60 Hz 1 phase motors10 hp at 230/240 V AC 50/60 Hz 3 phases motors30 hp at 575/600 V AC 50/60 Hz 3 phases motors3 hp at 115 V AC 50/60 Hz 1 phase motors10 hp at 200/208 V AC 50/60 Hz 3 phases motors30 hp at 460/480 V AC 50/60 Hz 3 phases motors
|
|
| control circuit type |
DC standard
|
|
| [Uc] control circuit voltage |
220 V DC
|
|
| auxiliary contact composition |
1 NO + 1 NC
|
|
| [Uimp] rated impulse withstand voltage |
Conforming to IEC 60947
|
|
| overvoltage category |
III
|
|
| [Ith] conventional free air thermal current |
60 A at <= 140 °F (60 °C) power circuit10 A at <= 140 °F (60 °C) signalling circuit
|
|
| Irms rated making capacity |
800 A at 440 V power circuit conforming to IEC 60947140 A AC signalling circuit conforming to IEC 60947-5-1250 A DC signalling circuit conforming to IEC 60947-5-1
|
|
| rated breaking capacity |
800 A at 440 V power circuit conforming to IEC 60947
|
|
| [Icw] rated short-time withstand current |
100 A 1 s signalling circuit120 A 500 ms signalling circuit140 A 100 ms signalling circuit320 A <= 104 °F (40 °C) 10 s power circuit720 A <= 104 °F (40 °C) 1 s power circuit72 A <= 104 °F (40 °C) 10 min power circuit165 A <= 104 °F (40 °C) 1 min power circuit
|
|
| associated fuse rating |
80 A gG at <= 690 V coordination type 1 power circuit80 A gG at <= 690 V coordination type 2 power circuit10 A gG signalling circuit conforming to IEC 60947-5-1
|
|
| average impedance |
1.5 mOhm at 50 Hz - Ith 60 A power circuit
|
|
| [Ui] rated insulation voltage |
600 V power circuit certifications CSA600 V power circuit certifications UL690 V power circuit conforming to IEC 60947-4-1690 V signalling circuit conforming to IEC 60947-1600 V signalling circuit certifications CSA600 V signalling circuit certifications UL
|
|
| electrical durability |
1.5 Mcycles 40 A AC-3 at Ue <= 440 V1.4 Mcycles 60 A AC-1 at Ue <= 440 V
|
|
| power dissipation per pole |
5.4 W AC-12.4 W AC-3
|
|
| protective cover |
With
|
|
| mounting support |
RailPlate
|
|
| standards |
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
|
|
| product certifications |
GOSTULCSACCC
|
|
| connections - terminals |
Control circuit: lugs-ring terminals - external diameter: 0.31 in (8 mm)Power circuit: lugs-ring terminals - external diameter: 0.65 in (16.5 mm)
|
|
| tightening torque |
Control circuit: 15.04 lbf.in (1.7 N.m) - on lugs-ring terminals - with screwdriver flat Ø 6 mm screw : M3.5Control circuit: 15.04 lbf.in (1.7 N.m) - on lugs-ring terminals - with screwdriver Philips No 2 screw : M3.5Power circuit: 53.1 lbf.in (6 N.m) - on lugs-ring terminals hexagonal 0.39 in (10 mm) screw : M6
|
|
| operating time |
16...24 ms opening42.5...57.5 ms closing
|
|
| safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
|
|
| mechanical durability |
10 Mcycles
|
|
| operating rate |
3600 cyc/h at <= 140 °F (60 °C)
|
|